IS 875 Explained: Structural Loads as per IS 875 & IS 1893

Spread the Knowledge, Share the Love ❤️

Structures are subjected to different types of loads throughout their service life. Indian Standards such as IS 875 and IS 1893 define how these loads are calculated, distributed, and combined to ensure safety and serviceability. The primary loads considered in building design are dead load, live (imposed) load, wind load, and earthquake (seismic) load.

Types of Loads in Structures as per IS 875 & IS 1893


Structures are designed to resist various types of loads during their lifetime. The key categories, as defined in Indian Standards, include:

  • Dead Load (IS 875 Part 1)
  • Live or Imposed Load (IS 875 Part 2)
  • Wind Load (IS 875 Part 3)
  • Earthquake or Seismic Load (IS 1893)

Dead Load


Dead loads are the permanent, static weights of the structure and its fixed components. They include the weight of beams, columns, slabs, walls, finishes, roofing, fixed equipment (e.g. HVAC, plumbing) and any permanently attached fixtures. Dead load is calculated simply as:

  • Dead Load (kN or N) = Unit Weight (kN/m³) × Volume (m³) of each element

The unit weights of materials are given in IS 875-1 (1987) as tabulated values (e.g. concrete ≈24 kN/m³, brickwork ≈20 kN/m³). IS 875 Part 1 lists standard weights of materials and stored materials for dead load calculations

Design considerations for dead load include: ensuring all permanent elements are accounted for (including “superimposed” dead loads like finishes and partition walls), and treating dead load as uniformly distributed gravity loads. Dead loads cannot be reduced or shifted; they are applied in ultimate limit state combinations Dead loads are applied with appropriate partial safety factors as specified in IS 875 and IS 456, depending on the governing load combination.

Basic Structural Load Terms (Fundamentals)

Live (Imposed) Load


Live loads are the variable or transient loads due to occupancy and use. They include people, furniture, movable equipment, vehicles (for bridges), and stored materials.

By definition these do not act simultaneously everywhere and can change in magnitude and location, dead loads remain constant, while live loads “vary with respect to the occupancy and activities” in the structure. Live loads are given in IS 875 (Part 2) as minimum specified loads for different occupancies.

Live load calculations follow the code procedure:

  • Use the minimum characteristic value from IS 875-2 for the given occupancy (e.g. offices, assembly, warehouse).
  • Assume live load as uniformly distributed load (UDL) unless concentrated loads are specified (e.g. machinery).

Live load reduction: For large floor areas or multiple floors, IS 875-2 permits reduction. Only the floors with live load are assumed loaded simultaneously. For multistory buildings, code allows reduced live load on columns depending on how many floors they support (e.g. 20% reduction if 3 floors above) (See IS 875-2 Table 3 for reduction factors.) However, IS 1893 (seismic) treats live loads differently for seismic weight calculations.

Live loads are combined with appropriate factors in design. In ultimate load combinations (e.g. 1.5D+1.5L+ …), live load is factored (often 1.5) as per IS 875. For serviceability (deflections, vibrations), unfactored live load (1.0×) is used. Impact and dynamic effects are included via additional factors if applicable (e.g. train loads, crane loads).

Wind Load (As per IS 875 Part 3:2015)

Wind load refers to the lateral (horizontal) force exerted by wind on structures. In Indian standards, wind loading is governed by IS 875 Part 3 (2015), which provides a static equivalent method for calculating design wind pressure based on basic wind speed and modifying factors.

Key Parameters for Wind Load Calculation:

Design Wind Speed at Height z

V_z = V_b \cdot k_1 \cdot k_2 \cdot k_3 \cdot k_4

Where:

Design Wind Pressure:

p_z = 0.6 \cdot V_z^2

Where:

Additional Modifiers:

These modifiers ensure accurate distribution of wind loads on various components of the structure.

Example Calculation:

For a 30 m tall building in Terrain Category II (urban environment):

V_z = 39 \cdot 1.0 \cdot 1.0 \cdot 1.0 \cdot 1.0 = 39 \, \text{m/s}
p_z = 0.6 \cdot (39)^2 = 0.6 \cdot 1521 = 912.6 \, \text{N/m}^2
p_z \approx 912.6 \, \text{N/m}^2

This design wind pressure is applied to the windward face and used for assessing uplift forces on roofs.

Design Considerations:

Earthquake (Seismic) Load (IS 1893: 2016)


Earthquake loads are lateral inertial forces caused by ground motion. IS 1893 (Part 1, 2016) governs the seismic design of structures in India. The country is divided into Seismic Zones II to V — from low to very high risk.

Factors Affecting Seismic Load

The total design seismic load depends on:

Design Seismic Base Shear

The equivalent static method is applicable to regular buildings within the height and plan limits specified in IS 1893; taller or irregular structures require dynamic analysis.

IS 1893 uses the Equivalent Static Method to estimate the design base shear Vb

V_b = A_h \cdot W

Where:

  • Vb​: Design base shear (in kN)
  • W: Seismic weight (in kN)
  • Ah​: Design horizontal seismic coefficient

Seismic Coefficient Formula

A_h = \frac{Z I}{2 R} \cdot \frac{S_a}{g}

Where:

  • Z: Zone factor
  • I: Importance factor
  • R: Response reduction factor
  • Sa/g​​: Spectral acceleration (dimensionless)

Fundamental Natural Period

The code provides empirical formulas to estimate the fundamental period T of a building. For reinforced concrete moment-resisting frames:

T = 0.075 \cdot h^{0.75}

Where:

  • T: Time period (in seconds)
  • h: Height of the building (in meters)

Distribution of Seismic Forces

Vertical Seismic Load

Vertical earthquake effects are usually ignored, unless the structure is:

Load Combinations

Design combinations typically include:

1.2 D + 1.2 E + 0.5 L

Where:

  • D: Dead load
  • E: Earthquake load
  • L: Live load

Other combinations may also be applicable as per IS 1893 and IS 456.

Example Calculation

For a building in Seismic Zone V, with:

Z = 0.36 \\
I = 1.5 \\
R = 5 \\
\frac{S_a}{g} = 2.5 \\
W = 10{,}000 \, \text{kN}
Step 1: Calculate Ah
A_h = \frac{0.36 \cdot 1.5}{2 \cdot 5} \cdot 2.5 = 0.135
Step 2: Calculate Vb
V_b = 0.135 \cdot 10{,}000 = 1{,}350 \, \text{kN}

This base shear of 1,350 kN is distributed among the floors based on their mass and height.

Design Considerations

Load Combinations and Design Considerations


In design, these loads are combined per IS 875/1893. The general ultimate load combination for buildings is:

Design CaseLoad Combination
Gravity (ULS)1.5D + 1.5L
Seismic (ULS)1.2D + 1.2E + 0.5L
Wind (ULS)1.5D + 1.5W
Serviceability1.0D + 1.0L (+ 0.5W/E)

Serviceability combinations (for deflection, vibration) often use 1.0D + 1.0L + 0.5W/E. Special considerations (impact, temperature, snow) are addressed in IS 875-5 but are beyond the main four loads.

Design and Code Terminology (IS 875 & IS 1893)

  1. Characteristic Load: The value of a load that is not expected to be exceeded during the life of a structure. For live loads, it’s typically taken as a representative value specified in IS 875 Part 2 based on occupancy.
  2. Uniformly Distributed Load (UDL): A load that is spread evenly across a surface or length, measured in kN/m² (for area) or kN/m (for length). Most live loads are assumed to be UDL unless otherwise mentioned.
  3. Concentrated Load: A load applied at a specific point, such as the weight of a heavy machine or equipment on a small area. Requires special treatment in design.
  4. Live Load Reduction: A reduction in the total live load considered on structural members like columns or foundations, especially in multi-story buildings. It accounts for the probability that not all floors will be fully loaded simultaneously. IS 875 Part 2 Table 3 provides guidelines.
  5. Impact Load / Dynamic Load: These loads arise from moving objects like cranes, vehicles, or machinery. They cause additional forces due to motion, vibration, or acceleration, and are added using special factors as per IS codes.
  6. Seismic Weight: The effective weight of the structure considered for earthquake load calculations. It includes full dead load and a portion of the live load, depending on the occupancy and usage type, as per IS 1893.
  7. Ultimate Load Combination: A set of combined loads (dead, live, wind, earthquake, etc.) used to check the structure under extreme or worst-case conditions. For example, 1.5D + 1.5L. Factors are defined in IS 875 Part 5 and IS 1893.
  8. Serviceability Limit State (SLS): Design criteria that ensure comfort and usability (e.g., limiting deflection, vibration, or cracking). Loads are taken without factors (1.0×) under this state.

Key design notes:

What are the major types of loads considered in structural design?

The primary loads in structural design include Dead Load, Live Load (Imposed Load), Wind Load, and Earthquake (Seismic) Load. These are governed by IS 875 Parts 1–3 and IS 1893:2016 for seismic design.

What is dead load as per IS 875 Part 1?

Dead load refers to the permanent self-weight of structural components like slabs, beams, columns, and non-movable fixtures. It is calculated using unit weights from IS 875 Part 1.

How is live load different from dead load?

Live load is transient and variable, such as the weight of occupants, furniture, or movable equipment. Unlike dead load, it changes over time and location, and is defined in IS 875 Part 2.

How do you calculate wind load as per IS 875 Part 3?

Wind load is calculated using the formula:
Pz = 0.6 × Vz²,
where Vz is the design wind speed, derived from basic wind speed (Vb) and modifying factors k1 to k4 based on terrain, height, topography, and cyclone zone.

What is seismic load and how is it calculated?

Seismic load is the lateral force due to ground motion during an earthquake. IS 1893:2016 provides an equivalent static method:
Vb = Ah × W,
where Vb is base shear, Ah is the design horizontal seismic coefficient, and W is the seismic weight.

Which IS code is used for earthquake design in India?

IS 1893:2016 (Part 1) governs the seismic analysis and design of buildings in India. It includes seismic zones, base shear calculations, and design response spectra.

What are typical live loads for buildings?

Live loads depend on occupancy:
Residential floors: 2.0 kN/m² (IS 875 Part 2)
Offices: 3.0 kN/m²
Shopping malls: 4.0 kN/m²
as per IS 875 Part 2.

Can live loads be reduced in design?

Yes. IS 875 Part 2 Table 3 allows live load reductions on columns and foundations when multiple floors contribute loads, assuming not all are fully loaded simultaneously.

Are wind and earthquake loads considered together?

No. As per IS codes, wind and seismic loads are not combined simultaneously. The structure is designed for whichever load case is more critical.

What is the difference between ULS and SLS?

ULS (Ultimate Limit State): Ensures the structure doesn’t collapse under maximum load conditions (e.g., 1.5D + 1.5L).
SLS (Serviceability Limit State): Ensures comfort and usability without excessive deflection or cracking (e.g., 1.0D + 1.0L).

What is meant by load combination in structural design?

Load combinations are specific sets of loads applied together to simulate real-world conditions. IS 875 and IS 1893 define combinations such as:
1.5D + 1.5L + 1.5E (earthquake) or
1.5D + 1.5L + 1.5W (wind).

Explore Civil Engineering Tools

Quick access to essential tools, formulas, and code references—all in one place.

AI Quick Search

Discover more from The Civil Studies

Subscribe now to keep reading and get access to the full archive.

Continue reading